EasyManua.ls Logo

York YLAA0180 - TABLE 3 - ETHYLENE AND PROPYLENE GLYCOL CORRECTION FACTORS

York YLAA0180
186 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
47
SECTION 5 – TECHNICAL DATA
FORM 150.72-ICOM7
ISSUE DATE: 10/22/2020
55
ETHYLENE GLYCOL PROPYLENE GLYCOL
%
WEIGHT
TONS
COMPR
KW
GPM F/
TON
PRESS
DROP
FREEZE
PT
%
WEIGHT
TONS
COMPR
KW
GPM F/
TON
PRESS
DROP
FREEZE
PT
10.0 1.0 1.0 24.3 1.0 26.2 10.0 1.0 1.0 24.0 1.0 26.0
20.0 1.0 1.0 25.1 1.1 17.9 20.0 1.0 1.0 24.3 1.1 19.0
30.0 1.0 1.0 25.9 1.2 6.7 30.0 1.0 1.0 24.9 1.3 9.0
40.0 1.0 1.0 26.9 1.4 -8.1 40.0 1.0 1.0 25.6 1.4 -6.0
50.0 1.0 1.0 28.0 1.6 -28.9 50.0 0.9 1.0 26.6 1.7 -28.0
NOTE: Water Pressure Drop Curves may extend past the minimum and maximum water ow ranges.
TABLE 3 - ETHYLENE AND PROPYLENE GLYCOL CORRECTION FACTORS