51
SECTION 5 – TECHNICAL DATA
FORM 150.72-ICOM7
ISSUE DATE: 10/22/2020
55
ELECTRICAL DATA
TABLE 6 - MICROPANEL POWER SUPPLY
UNIT VOLTAGE
UNIT
VOLTAGE
CONTROL
POWER
MCA
NOTE A
OVER CURRENT PROTECTION,
SEE NOTE B
NF DISC SW
MIN MAX
MODELS W/O
CONTROL
TRANS
115-1-60/50
15 A 10 A 15 A 30 A / 240V
MODELS W/
CONTROL
TRANS
-17 200-1-60 15 A 10 A 15 A 30 A / 240 V
-28 230-1-60 15 A 10 A 15 A 30 A / 240 V
-40 380-1-60 15 A 10 A 15 A 30 A / 480 V
-46 460-1-60 15 A 10 A 15 A 30 A / 480 V
-50 380/415-1-50 15 A 10 A 15 A 30 A / 415 V
-58 575-1-60 15 A 10 A 15 A 30 A / 600 V
NOTE: A. Minimum #14 AWG, 75 °C, Copper Recommended.
B. Minimum and Maximum Over Current Protection, Dual Element Fuse or Circuit Breaker.
Voltage Limitations
The following voltage limitations are absolute and
operation beyond these limitations may cause serious
damage to the compressor.
TABLE 7 - VOLTAGE RANGE
VOLTAGE RANGE
VOLTAGE CODE UNIT POWER MIN. MAX.
-17 200-208/3/60 187 228
-28 230-3-60 207 253
-40 380-3-60 355 415
-46 460-3-60 414 506
-50 380/415-3-50 360 440
-58 575-3-60 517 633
COMPRESSOR HEATERS
Compressor heaters are standard. ZP180 compressors
use 70 W heaters; ZP235, compressor use 120 W heat-
ers and ZP285 and ZP385 use 150 W heaters. If power
is OFF more than two hours, the crankcase heaters must
It is possible that multiple sources of
power can be supplying the unit power
panel. To prevent serious injury or death,
the technician should verify that NO
LETHAL VOLTAGES are present inside
the panel AFTER disconnecting power,
BEFORE working on equipment.
The unit evaporator heater uses 110 VAC.
Disconnecting 120 VAC power from the
unit, at or below freezing temperatures,
can result in damage to the evaporator
and unit as a result of the chilled liquid
freezing.
be energized for 18 hours to 24 hours before restarting
a compressor. This will ensure that liquid slugging and
oil dilution does not damage the compressors on start.