SECTION 5 – TECHNICAL DATA
FORM 150.72-ICOM7
ISSUE DATE: 10/22/2020
55
REFRIGERANT
R-410A
YLAA
HIGH EFFICIENCY UNITS
GENERAL UNIT DATA 0195HE 0221HE 0262HE 0301HE 0350HE 0392HE 0442HE 0457HE 0517HE
Nominal Capacity (kW) 197.9 211.1 243.9 297.2 347.6 379.2 431.2 457.1 525
COP (kW/kW) 3.12 3.23 3.06 3.00 2.96 2.98 2.95 2.95 2.95
IPLV (kW/kW) 4.94 4.85 4.69 4.62 4.58 4.98 4.83 4.80 4.96
Length (mm) 2911 2911 2911 3690 3690 3690 4807 4807 4807
Width (mm) 2242 2242 2242 2242 2242 2242 2242 2242 2242
Height (mm) 2393 2393 2393 2393 2393 2393 2393 2393 2393
REFRIGERANT CHARGE, OPERATING
Number of Refrigerant
Circuits
2 2 2 2 2 2 2 2 2
Refrigerant Charge,
Circuit 1/Circuit 2 (kg)
24.0/16.8 24.5/22.7 24.0/24.0 24.5/28.1 28.6/26.8 29.1/29.1 37.6/28.1 36.7/35.4 39.5/39.0
Oil Charge,
Circuit 1/Circuit 2 (liter)
9.6/5.4 9.6/6.4 9.6/9.6 9.6/10.6 10.6/10.6 16.0/10.6 16.0/10.6 16.0/16.0 16.0/16.0
Shipping Weight (kg) 1681 1696 1818 2087 2301 2467 3294 3443 3560
Operating Weight (kg) 1706 1721 1852 2120 2339 2517 3343 3481 3615
COMPRESSORS, SCROLL TYPE
Compressor Number,
Circuit 1/Circuit 2
(piece)
3 / 2 3 / 2 3 / 3 3 / 2 2 / 2 3 / 2 3 / 2 3 / 3 3 / 3
MCHX CONDENSER & FANS
Total Face Area (m
2
) 10.0 10.0 10.0 12.5 15.1 15.1 17.6 20.1 20.1
Number of Rows 1 1 1 1 1 1 1 1 1
Number of Fans,
Circuit 1/Circuit 2
(piece)
2 / 2 2 / 2 2 / 2 2 / 3 3 / 3 3 / 3 4 / 3 4 / 4 4 / 4
Fan Power (hp) 2 2 2 2 2 2 2 2 2
Fan RPM 950 950 950 950 950 950 950 950 950
Total Air Flow Rate
(m
3
/s)
20 28 28 35 42 42 50 57 57
EVAPORATOR, BPHX
Water Volume (liter) 25.2 25.2 33.2 33.2 38 50 50 38 54
Maximum Water Side
Pressure (bar)
10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3
Maximum Refrigerant
Side Pressure (bar)
31 31 31 31 31 31 31 31 31
Water Connections
Size (inch)
3 3 3 3 3 3 4 4 4
NOTES:
1. kW = Compressor Input Power.
2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW).
3. Rated in accordance with AHRI Standard 550/590 at an air on condenser temperature of 95°F and a leaving chilled water temperature of 44°F.
4. Additional rating information can be provided by your local Johnson Controls Sales O󰀩ce.
TABLE 5 - PHYSICAL DATA (ENGLISH) - HIGH EFFICIENCY UNITS