JOHNSON CONTROLS
48
FORM 150.72-ICOM7
ISSUE DATE: 10/22/2020
SECTION 5 – TECHNICAL DATA
REFRIGERANT
R-410A
YLAA
STANDARD EFFICIENCY UNITS
GENERAL UNIT DATA 0180SE 0210SE 0241SE 0286SE 0320SE 0360SE 0400SE 0435SE 0485SE
Nominal Capacity (kW) 189.5 206.6 218.2 273.1 312.6 350.9 391.5 423.8 477.5
COP (kW/kW) 3.00 2.42 2.77 2.63 2.43 2.58 2.44 2.58 2.47
IPLV (kW/kW) 4.66 3.99 4.25 4.52 4.29 4.51 4.41 4.51 4.44
Length (mm) 2911 2911 2911 2911 2911 3690 3690 3690 3690
Width (mm) 2242 2242 2242 2242 2242 2242 2242 2242 2242
Height (mm) 2393 2393 2393 2393 2393 2393 2393 2393 2393
REFRIGERANT CHARGE, OPERATING
Number of Refrigerant
Circuits
2 2 2 2 2 2 2 2 2
Refrigerant Charge,
Circuit 1/Circuit 2 (kg)
21.3/15.4 22.2/14.5 21.3/21.3 24.0/25.9 25.9/25.9 30.4/24.0 30.8/26.8 30.8/29.0 31.8/30.4
Oil Charge,
Circuit 1/Circuit 2 (liter)
9.6/5.4 10.6/5.4 9.6/9.6 9.6/10.6 10.6/10.6 16.0/9.6 16.0/10.6 16.0/16.0 16.0/16.0
Shipping Weight (kg) 1661 1704 1764 1828 1904 2781 2834 2604 2704
Operating Weight (kg) 1681 1725 1784 1853 1937 2814 2872 2642 2755
COMPRESSORS, SCROLL TYPE
Compressor Number,
Circuit 1/Circuit 2
(piece)
3/2 2/2 3/3 3/2 2/2 3/3 3/2 3/3 3/3
MCHX CONDENSER & FANS
Total Face Area (m
2
) 10.0 10.0 10.0 10.0 10.0 12.5 12.5 15.1 15.1
Number of Rows 1 1 1 1 1 1 1 1 1
Number of Fans,
Circuit 1/Circuit 2
(piece)
2/2 2/2 2/2 2/2 2/2 3/2 3/2 3/3 3/3
Fan Power (hp) 2 2 2 2 2 2 2 2 2
Fan RPM 950 950 950 950 950 950 950 950 950
Total Air Flow Rate
(m
3
/s)
20 20 28 28 28 35 35 42 42
EVAPORATOR, BPHX
Water Volume (liter) 20.4 20.4 20.4 25.2 33.2 33.2 38.0 38.0 50.0
Maximum Water Side
Pressure (bar)
10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3
Maximum Refrigerant
Side Pressure (bar)
31 31 31 31 31 31 31 31 31
Water Connections
Size (inch)
3 3 3 3 3 3 3 3 3
NOTES:
1. kW = Compressor Input Power.
2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW).
3. Rated in accordance with AHRI Standard 550/590 at an air on condenser temperature of 95°F and a leaving chilled water temperature of 44°F.
4. Additional rating information can be provided by your local Johnson Controls Sales O󰀩ce.
PHYSICAL DATA YLAA0180 YLAA0517 50 HZ
TABLE 4 - PHYSICAL DATA (ENGLISH) - STANDARD EFFICIENCY UNITS