EasyManua.ls Logo

York YLAA0180 - REMOTE BAS;EMS TEMPERATURE RESET USING A VOLTAGE OR CURRENT SIGNAL

York YLAA0180
186 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
165
SECTION 8 – UNIT OPERATION
FORM 150.72-ICOM7
ISSUE DATE: 10/22/2020
8
REMOTE BAS/EMS TEMPERATURE RESET
USING A VOLTAGE OR CURRENT SIGNAL
The Remote Reset Option allows the Control Center
of the unit to reset the chilled liquid set point using a
0 to 10 VDC input, or a 4 mA to 20 mA input con-
nected to XTBC1 Terminals A- and A+. Whenever a
reset is called for, the change may be noted by pressing
the COOLING SET POINTS key twice. The new value
will be displayed as “REM SETP = XXX °F.”
If a 0 VDC to 10 VDC signal is supplied, it is applied
to Terminals A+ and A-, and jumper JP1 on the I/O
board must be inserted between pins 2 and 3. To calcu-
late the reset chilled liquid set point for values between
0 VDC and 10 VDC use the following formula:
Set Point = Local Chilled Liquid Set Point + °Reset
°Reset = (DC voltage signal) x (*Max Reset Value)
10
Example:
Local Chilled Liquid Set Point = 45°F (7.22°C)
*Max Reset Value = 20°F (11.11°C)
Input Signal = 6 VDC
(English)
°Reset = 6 VDC x 20°F
10
New Set Point = 45°F + 12°F = 57°F
(Metric)
°Reset = 6 VDC x 11.11°C
10
New Set Point = 7.22°C + 6.67°C = 13.89°C
* Max Reset Value is the “Max EMS-PWM Remote Temp. Reset”
set point value described in “Remote Set Point Control” on page
124 under “Cooling Set Points”. Programmable values are from
2°F to 40°F (1.11°C to 11.11°C).
= 12°F Reset
= 6.67°C Reset
If a 4 mA to 20 mA signal is supplied, it is applied to
Terminals A+ and A- and jumper JP1 on the I/O board
must be installed between pin 1 and 2. To calculate the
chilled liquid set point for values between 4 mA and 20
mA use the following formula:
Set Point = Local Chilled Liquid Set Point + °Reset
°Reset = (mA signal - 4) x (*Max Reset Value)
16
Example:
Local Chilled Liquid Set Point = 45°F (7.22°C)
*Max Reset Value = 10°F (5.56°C)
Input Signal = 12 mA
(English)
°Reset = 8 mA x 10°F
16
Set Point = 45°F + 5°F = 50°F
(Metric)
°Reset = 8 mA x 5.56°C
16
Set Point = 7.22°C + 2.78°C = 10.0°C
= 5°F Reset
= 2.78°C Reset
A 240 to 24 Volt Ratio Transformer (T3) is
used to derive nominal 12 V output from
the 120 V supply.

Table of Contents

Related product manuals