EasyManua.ls Logo

York YLAA0180 - OPTIONAL PRINTER INSTALLATION; Parts

York YLAA0180
186 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
177
SECTION 9 – SERVICE AND TROUBLESHOOTING
FORM 150.72-ICOM7
ISSUE DATE: 10/22/2020
9
OPTIONAL PRINTER INSTALLATION
The micro panel is capable of supplying a printout
of chiller conditions or fault shutdown information at
any given time. This allows operator and service per-
sonnel to obtain data and system status with the touch
of the keypad. In addition to manual print selection,
the micro panel will provide an automatic printout
whenever a fault occurs. Detailed explanation of the
print function is given under Print Key on page 117.
Parts
The following parts are required:
1. Printer.
2. Desk top calculator paper, 2.25 in. (5.7 cm) wide.
3. Twisted Pair Shielded Cable (minimum 3 conduc-
tor), #18 AWG stranded, 300 V minimum insula-
tion, 25 ft (7.62 m) maximum length.
4. One 25 pin Cannon connector and shell.
5. Cannon P/N DB-25P connector, or equivalent.
6. Cannon P/N DB-C2-J9 shell.
TABLE 35 - DATA LOGGING TO FLASH (CONT’D)
DATA
NUMBER
HEADER DATA
TEXT UNIT FORMAT VALUE DESCRIPTION
75 S1 Prop Cont In x
Sys 1 CSHALG_PROPORTIONAL_CONTRIBUTION_INDEX
(0-10000 in x100 format)
76 S1 Int Cont In x
Sys 1 CSHALG_INTEGRAL_CONTRIBUTION_INDEX
(0-1000000 in x10000 format)
77 S1 Der Cont In x
Sys 1 CSHALG_DERIVATIVE_CONTRIBUTION_INDEX
(0-10000 in x100 format)
78 S2 Full PID Index x
Sys 2 CSHALG_FULL_PID_ACTIVE_INDEX
(0 = Disable, 1 = Active)
79 S2 Dim PID Index x
Sys 2 CSHALG_DIMINISHED_PID_ACTIVE_INDEX
(0 = Disable, 1 = Active)
80 S2 Alg Ctrl Act x
Sys 2 CSHALG_ALGORITHM_CONTROL_ACTIVE
(0 = Disable, 1 = Enable)
81 S2 Sheat Ex In x
Sys 2 CSHALG_SUPERHEAT_EXCURSIONS_INDEX
(0 – 255 in x1 format)
82 S2 Prop Cont In x
Sys 2 CSHALG_PROPORTIONAL_CONTRIBUTION_INDEX
(0-10000 in x100 format)
83 S2 Int Cont In x
Sys 2 CSHALG_INTEGRAL_CONTRIBUTION_INDEX
(0-1000000 in x10000 format)
84 S2 Der Cont In x
Sys 2 CSHALG_DERIVATIVE_CONTRIBUTION_INDEX
(0-10000 in x100 format)
85 S1 Thr Limit % x Sys 1 CSHALG_EEV_THROTTLE_LIMIT (0-10000 in x100 format)
86 S2 Thr Limit % x Sys 2 CSHALG_EEV_THROTTLE_LIMIT (0-10000 in x100 format)