JOHNSON CONTROLS
58
FORM 150.72-ICOM7
ISSUE DATE: 10/22/2020
SECTION 5 – TECHNICAL DATA
ELECTRICAL NOTES AND LEGEND (CONT’D)
GENERAL
a. This drawing is based on IEC symbols.
b. Field wiring to be in accordance with the relevant electrical code as well as all other applicable codes and specications.
c. All sources of supply shown on this diagram to be taken from one main isolator, not shown or supplied by YORK.
d.
Green and yellow wire is used for earth, multi-colored cable used for low voltage. Red wire used for AC Control, blue wire for
neutral, black wire for AC and DC power. Orange wire should be used for interlock control wiring supplied by external source.
e.
Legend designation depicts component abbreviations. Number prex located, if applicable, on schematic circuit, refers to
system thereon, E.G. = 1-FHP2 refers to high pressure cutout no 2 on system no 1.
f.
All wiring to control section voltage free contacts requires a supply provided by the customer maximum voltage 240 volts.
The customer must take particular care when deriving the supplies for the voltage free terminals with regard to a common
point of isolation. Thus, these circuits when used must be fed via the common point of isolation. The voltage to these circuits
is removed when the common point of isolation to the unit is opened. This common point of isolation is not supplied by
YORK. The YORK voltage free contacts are rated at 100 VA. All inductive devices {relays} switch by the YORK voltage free
contacts must have their coil suppressed using standard R/C suppressors.
g. Customer voltage free contacts connected to terminal 13 must be rated at 30 V 5 mA.
h.
No controls {relays etc.} Should be mounted in any section of the control panel. Additionally, control wiring not connected
to the YORK control panel should not be run through the panel. If these precautions are not followed, electrical noise could
cause malfunctions or damage to the unit and its controls.
I. 120/14.3 - (Signal IN/OUT) i.e. 120 is wire # and 14.3 refers to SHT. 14 column 3.
NOTES
1
Refer to installation commissioning operation and maintenance manual for customer connections and customer connection
notes, non compliance to these instructions will invalidate unit warranty.
2
Wiring and components for compressor 3 only tted when unit has 3 compressors on the system. 1-BMP3 is replaced by a
link across terminals 134 & 135. 2-BMP3 is replaced by a link across terminals 234 & 235.
3 -
4 Fitted on units with hot gas bypass option.
5 EMS option is wired as shown.
6 This wiring must be used for old display 031-0110-000.
7 Network connection point.
8 Printer port.
9 Remote emergency stop can be wired between terminal 1 and 5 after removing link.
10 Power factor correction accessory. Power factor correction tted to each compressor contactor.
11
Not tted on compressors with internal motor protection. For system 1, terminals 132 & 133, 133 & 134, and 134 & 135 are
linked. For system 2, terminals 232 & 233, 233 & 234, and 234 & 235 are linked.
12 Only tted on systems with 3 or more fans.
13 Only tted on systems with 4 fans.
14 Only tted on systems with 5 fans.
15 Only tted on systems with 6 fans.
16 Input switch disconnect (standard on CE units) or circuit breaker option replaces input terminal block.
17 Input switch disconnect & individual system circuit breaker option replaces input terminal block.
18 115 V control circuit requires a 115 V supply unless control circuit transformer -T2 & -F3 are tted (standard on CE units).
19
Fitted on hydro kit option. On single pump -KP1, -QMMSP1 & -MP1 are tted & wired as shown. On two pump hydro kits
-KP2, -QMMSP2 & -MP2 are also tted and wired as shown. Insulated wire 1E under -F1 is connected to -F1.
20 Current measurement option wired as shown.
21 Only tted on systems with single speed fans.
22 Only tted on systems with two speed fans.
23 Optional compressor manual motors starters (standard on CE units).
24 See sheet 3 of connection diagram for power input options.
25 Alternate connections shown for di󰀨erent two speed motor types.
26 Only tted on systems with a maximum of 4 fans.
27 220/230 V units require a separate fuse for units with 4 or more fans per system.
28 Low ambient kit -FSC for fan -MF1 is only tted on systems with less than 4 fans.
29 Only tted on YLAA0091, 0220, 0240, 0260 and YLUA0098, 0308
30 Only tted on YLAA0090, 0091, 0240, 0260, 0285, 0300, 0390 & YLUA0095, 0098, 0148, 0298, 0308, 0468
31 Input dual point circuit breaker option replaces input terminal block.