EasyManua.ls Logo

York YLAA0180 - DIMENSIONS; FOUR FAN UNITS

York YLAA0180
186 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
80
FORM 150.72-ICOM7
ISSUE DATE: 10/22/2020
SECTION 5 – TECHNICAL DATA
FOUR FAN UNITS
DIMENSIONS – YLAA0180SE, YLAA0195HE, YLAA0210SE
DIMENSIONS
035-24059-015 REV-A
LD23529
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airow
patterns and possible diminished performance. Johnson Controls’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit
is no higher than on spring isolators. Recommended minimum clearances: Side to wall – 2 m (6 ft); rear to wall – 2 m (6 ft); control panel
to end wall – 1.2 m (4 ft); top – no obstructions allowed; distance between adjacent units – 10 ft. No more than one adjacent wall may be
higher than the unit.

Table of Contents

Related product manuals