SECTION 5 – TECHNICAL DATA
FIVE FAN UNITS
DIMENSIONS – YLAA0301HE, YLAA0360SE, YLAA0400SE
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airow
patterns and possible diminished performance. Johnson Controls’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit
is no higher than on spring isolators. Recommended minimum clearances: Side to wall – 2 m (6 ft); rear to wall – 2 m (6 ft); control panel
to end wall – 1.2 m (4 ft); top – no obstructions allowed; distance between adjacent units – 10 ft. No more than one adjacent wall may be
higher than the unit.
LD27952
035-24059-005 REV E