SECTION 1 - OVERVIEW
FORM 160.84-N1
ISSUE DATE: 11/22/2016
1
The chiller is shipped in two assemblies as follows:
1. The chiller unit (less the VSD).
2. The VSD.
3. Refrigerant charges shipped separately.
4. Miscellaneous shipped loose items.
Arrangements with the local service office must be
made to ensure refrigerant is on-site when the unit is
ready to be charged.
Chiller Unit
The unit is first completely assembled at the factory:
The driveline (compressor/motor assembly) is
mounted, with all necessary interconnecting pip-
ing assembled.
Interconnecting piping is assembled and the com-
plete unit is factory leak-tested then evacuated
and shipped charged with a 3 to 7 PSIG (20 to 50
kPa) holding charge of dry nitrogen.
The Motor Terminal Box adapter remains at-
tached to the chiller unit.
Variable Speed Drive (VSD)
The VSD is skidded and shipped separately from the
assembled chiller.
The VSD is lled with glycol for shipping. The
VSD operating coolant (inhibited water) shipped
with the other loose items.
Miscellaneous Material
The following assemblies and items are shipped to-
gether:
Four (4) vibration isolation pads (or optional
spring isolators and brackets).
Other shipped loose items, including piping, wa-
ter temperature controls, wiring, etc.
VSD operating coolant (inhibited water)
Form 10
Prior to shipping, the unit is completely assembled at
the factory. Interconnecting piping is assembled and
the complete unit is wired and leak-tested.
The chiller is shipped in two assemblies:
1. The assembled chiller unit.
2. The VSD.
3. Refrigerant charges are included.
4. Miscellaneous shipped loose items.
Chiller Unit
The unit is first completely assembled at the factory:
The driveline (compressor/motor assembly) is
mounted, with all necessary interconnecting pip-
ing assembled.
The complete unit is factory leak-tested, evacu-
ated, and shipped charged with refrigerant.
The Motor Terminal Box adapter remains at-
tached to the chiller unit.
Variable Speed Drive (VSD)
The VSD is skidded and shipped separately from the
assembled chiller.
The VSD is lled with glycol for shipping. The
VSD operating coolant (inhibited water) shipped
with the other loose items.
Miscellaneous Material
The following assemblies and items are shipped to-
gether:
Four (4) vibration isolation pads (or optional
spring isolators and brackets).
Other shipped loose items, including piping, wa-
ter temperature controls, wiring, etc.
VSD operating coolant (inhibited water)

Table of Contents

Other manuals for York YMC2

Related product manuals