SECTION 4 - INSTALLATION
JOHNSON CONTROLS
59
Form 201.47-ICOM1
Issue date: 17/11/2022
4
Table 4 - Electrical lug data (cont'd)
EBM CONDENSER FANS
FIELD WIRING LUGS TERMINAL BLOCK CIRCUIT BREAKER NON-FUSED DIS-
CONNECT SWITCH
YVAA-B MODEL EVAP INPUT
VOLTS
INPUT
FREQ
WIRES
PER
PHASE
LUG
WIRE
RANGE
WIRES
PER
PHASE
LUG
WIRE
RANGE
WIRES
PER
PHASE
LUG
WIRE
RANGE
SINGLE POINT WIRING
YVAA0259/0919 2005 200 60 4 #1/0 ~
700 kcmil
230 60 4 #2 – 600
kcmil
4 4/0 ~ 500
kcmil
380 60 3 #2 – 600
kcmil
3 3/0 ~ 400
kcmil
3 #2 ~ 600
kcmil
400 50 3 #2 – 600
kcmil
3 3/0 ~ 400
kcmil
3 #2 ~ 600
kcmil
460 60 3 #2 – 600
kcmil
3 3/0 ~ 400
kcmil
3 #2 ~ 600
kcmil
575 60 2 #2 – 600
kcmil
2 #1 – 500
kcmil
2 #2 ~ 600
kcmil
YVAA0266/0936 2205 200 60 4 #1/0 ~
700 kcmil
230 60 4 #2 – 600
kcmil
4 4/0 ~ 500
kcmil
380 60 3 #2 – 600
kcmil
3 3/0 ~ 400
kcmil
3 #2 ~ 600
kcmil
400 50 3 #2 – 600
kcmil
3 3/0 ~ 400
kcmil
3 #2 ~ 600
kcmil
460 60 3 #2 – 600
kcmil
3 3/0 ~ 400
kcmil
3 #2 ~ 600
kcmil
575 60 2 #2 – 600
kcmil
2 #1 – 500
kcmil
2 #2 ~ 600
kcmil
YVAA0219/0769 2004 200 60 4 #1/0 ~
700 kcmil
230 60 4 #2 – 600
kcmil
4 4/0 ~ 500
kcmil
380 60 3 #2 – 600
kcmil
3 3/0 ~ 400
kcmil
3 #2 ~ 600
kcmil
400 50 3 #2 – 600
kcmil
3 3/0 ~ 400
kcmil
3 #2 ~ 600
kcmil
460 60 2 #2 – 600
kcmil
2 #1 ~ 500
kcmil
3 #2 ~ 600
kcmil
575 60 2 #2 – 600
kcmil
2 #1 ~ 500
kcmil
2 #2 ~ 600
kcmil
YVAA0229/0809 2005 200 60 4 #1/0 ~
700 kcmil
230 60 4 #2 – 600
kcmil
4 4/0 ~ 500
kcmil
380 60 3 #2 – 600
kcmil
3 3/0 ~ 400
kcmil
3 #2 ~ 600
kcmil
400 50 3 #2 – 600
kcmil
3 3/0 ~ 400
kcmil
3 #2 ~ 600
kcmil
460 60 2 #2 – 600
kcmil
2 #1 ~ 500
kcmil
3 #2 ~ 600
kcmil
575 60 2 #2 – 600
kcmil
2 #1 ~ 500
kcmil
2 #2 ~ 600
kcmil