Issue date: 17/11/2022
Table 4 - Electrical lug data (cont'd)
EBM CONDENSER FANS
FIELD WIRING LUGS TERMINAL BLOCK CIRCUIT BREAKER NON-FUSED DIS-
CONNECT SWITCH
YVAA-B MODEL EVAP INPUT
VOLTS
INPUT
FREQ
WIRES
PER
PHASE
LUG
WIRE
RANGE
WIRES
PER
PHASE
LUG
WIRE
RANGE
WIRES
PER
PHASE
LUG
WIRE
RANGE
SINGLE POINT WIRING
YVAA0264/0924 2005 200 60 4 #1/0 ~
700 kcmil
230 60 4 #2 – 600
kcmil
4 4/0 ~ 500
kcmil
380 60 3 #2 – 600
kcmil
3 3/0 ~ 400
kcmil
3 #2 ~ 600
kcmil
400 50 3 #2 – 600
kcmil
3 3/0 ~ 400
kcmil
3 #2 ~ 600
kcmil
460 60 3 #2 – 600
kcmil
3 3/0 ~ 400
kcmil
3 #2 ~ 600
kcmil
575 60 2 #2 – 600
kcmil
2 #1 – 500
kcmil
2 #2 ~ 600
kcmil
YVAA0269/0949 2205 200 60 4 #1/0 ~
700 kcmil
230 60 4 #2 – 600
kcmil
4 4/0 ~ 500
kcmil
380 60 3 #2 – 600
kcmil
3 3/0 ~ 400
kcmil
3 #2 ~ 600
kcmil
400 50 3 #2 – 600
kcmil
3 3/0 ~ 400
kcmil
3 #2 ~ 600
kcmil
460 60 3 #2 – 600
kcmil
3 3/0 ~ 400
kcmil
3 #2 ~ 600
kcmil
575 60 2 #2 – 600
kcmil
2 #1 – 500
kcmil
2 #2 ~ 600
kcmil
YVAA0246/0866 2005
380 60 4 #2 – 600
kcmil
4 4/0 ~ 500
kcmil
4 #2 ~ 600
kcmil
400 50 4 #2 – 600
kcmil
4 4/0 ~ 500
kcmil
4 #2 ~ 600
kcmil
460 60 3 #2 – 600
kcmil
4 4/0 ~ 500
kcmil
3 #2 ~ 600
kcmil
575 60 3 #2 – 600
kcmil
3 3/0 ~ 400
kcmil
2 #2 ~ 600
kcmil
YVAA0324/1134 2205 200 60
230 60
380 60 4 #2 – 600
kcmil
4 4/0 ~ 500
kcmil
4 #2 ~ 600
kcmil
400 60 4 #2 – 600
kcmil
4 4/0 ~ 500
kcmil
4 #2 ~ 600
kcmil
400 50 4 #2 – 600
kcmil
4 4/0 ~ 500
kcmil
4 #2 ~ 600
kcmil
460 60 3 #2 – 600
kcmil
4 4/0 ~ 500
kcmil
4 #2 ~ 600
kcmil
575 60 3 #2 – 600
kcmil
3 3/0 ~ 400
kcmil
4 #2 ~ 600
kcmil