Long Press Threshold Time [5…50 ds]: sets the minimum time the user
should hold the button in order to consider it a long press. The available
range is 5 to 50 tenths of a second, being 5 tenths the default value.
Action on Short Press [Left=0; Right=1/Left=1; Right=0]: sets the value that
will be sent through [Btn] [PX] Two objects - Short press after the user
short-presses one of the two buttons.
Note: this parameter will remain hidden unless having selected Every button
pair is configured separately” in Action of the pair buttons.
Action on Long Press [Left=0; Right=1/Left=1; Right=0]: sets the value that
will be sent through [Btn] [PX] Two objects - Long press after the user
long-presses one of the two buttons.
Note: this parameter will remain hidden unless having selected Every button
pair is configured separately” in Action of the pair buttons.
LED Illumination Control [State-dependent/Regular/State-dependent (both
LEDs)/Dedicated Object]: analogous to the homonymous parameter for the
“Switch” function (see above). In this case, however, selecting State-
dependent” or State-dependent (both LEDs)” brings an additional parameter,
State Object, to make the state of the LEDs correspond either to object
[Btn] [PX] Two objects - Short press (“Short Press Object”) or to object
[Btn] [PX] Two objects - Long press” (“Long Press Object”).
Dimmer
Figure 31 Pair Buttons - Dimmer.
The parameters for this function are: