EasyManua.ls Logo

Zeta Alarm Systems Simplicity Plus 252 - Setting Individual I;O Unit Output Operation; Setting Individual I;O Unit Input Operation

Default Icon
50 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SIMPLICITY PLUS INSTALLATION MANUAL
Approved Document No: GLT.MAN-107 PAGE 28
Issue 3.16 Author: NRPJ Date: 21/09/2017
Select Option 3 (Alarms) to bring up the alarm operation Menu.
Select option 5 (I/O). This brings up the following screen.
Alarm Operation
1: Det 4: Bases
2: MCP 5: I/O
3: Sounder
Press Prev & Next to select the default operation, then press enter.
I/O Unit Operation
Common
ENTER to Confirm
12.9.3 SETTING INDIVIDUAL I/O UNIT OUTPUT OPERATION
To alter the operation mode of an individual I/O unit, go to configuration menu 2.
Select Edit Device.
Configuration Menu 2
4:Configure Loops
5:Edit Device
6:Config System <
Scroll to the required Address.
Press V to cycle through the different Variations of I/O configuration.
I/O-COM
Analog: 16 Normal
Interface to Main FA
Zone:01 Ad:013
12.9.4 SETTING INDIVIDUAL I/O UNIT INPUT OPERATION
To alter the INPUT mode of an individual I/O unit, go to configuration menu 2
Select Edit Device.
Scroll to the required Address
Press Button ā€œIā€ (for Input) to cycle through the different Triggering Options of I/O configuration
The different options are:-
Letter Description Use
A AUTOMATIC ALARM I/O signals Detector alarm when operated. Default setting. Used when
device being monitored is Automatically triggered.
M MANUAL CALL POINT ALARM I/O signals a MCP alarm when operated. Used when device being
monitored is Manually triggered, and the system is set to distinguish
manual & automatic alarms.
P PREALARM I/O signals a Pre-Alarm when operated. Used when a device being
monitored needs to give a warning signal , but not an alarm signal.
F FAULT I/O signals a Fault Signal when operated. Used when a device being
monitored does not have a normally closed fault relay
D DISABLE RELAYS I/O sets all connected I/O relays as disabled when operated. Used when
user testing of the panel needs to suspend relay operation to avoid
shutting down connected equipment. Turning off the input re-enables the
relays
I/O Zn-D
P
Normal
Plant Room
Zone:01 ID:
01

Table of Contents

Related product manuals