1.2 I Technical specicaons
Z950 TD35 TD45 TD60 TD90 TD120
Operang temperatures
air -12 to 38 °C
water 10 to 40 °C
Defrosng by cycle inversion Air T°C < 10 °C
Voltage 400V/3/50 Hz
Admissible variaon in voltage ± 10 % (during operaon)
Polluon class I
Polluon degree 2
Overvoltage category II
Protecon fuse (F, quick) 10 A / 250 V
Protecon rang IP44
Refrigerant gas R410-A kg 6 7.5 9 2 x 9 2 x 11
Minimum cable secon* mm² 4 6 10 16 25
Proof pressure bar 3
Service pressure bar 1.5
Maximum inlet pressure bar 3.5
Head loss KPa 15 50 41.6 52 74
Recommended water ow rate m³/h 13 20 30 42 60
Acousc power db(A)** 83 83 90 90 90
Acousc pressure at 10 m db(A)** 52 52 58 58 58
Net weight kg 185 210 287 447 500
Gross weight kg 195 220 310 475 545
PERFORMANCE: 15 °C air / 26 °C water / Humidity : 70%
Power consumed kW 6.20 8.10 11.50 16.80 23.90
Power output kW 30.53 39.70 56.80 80.20 110.50
Average COP 4.92 4.90 4.94 4.77 4.62
PERFORMANCE: 28 °C air / 28 °C water / Humidity : 80%
Power consumed kW 6.93 8.53 12.25 17.6 24.97
Power output kW 39.48 47.94 68.1 98.1 133.1
Average COP 5.69 5.62 5.54 5.56 5.32
* Values provided for informaon purposes for a maximum length of 20 metres (calculaon base: NFC15-100), must be checked and adapted to the
installaon condions and standards of the installaon country.
** In accordance with the standards UNE-EN 12102 / ISO 3744:2010