28
If F24 = 1 (only one compressor), the system 2 inputs and outputs are not used and no value is displayed.
5.4 I Advanced operang principles
5.4.1 Operang principles of modes
The appliance has 4 operang modes: Heang, Cooling, Heang/Cooling. The user interface can be used to switch
between these modes (see § "”3.2 I User interface presentaon”) or by modifying the value of the advanced F29
parameter (see § “5.3 I Advanced seng parameters (accessible by a qualied technician)”).
5.4.1.1 Heang mode
In Heang mode, the appliance heats the water when the sensor temperature is lower than the setpoint temperature
reduced by the temperature dierenal. The appliance stops heang the water when the temperature is higher than the
setpoint temperature increased by the temperature dierenal (see following sequences.)
5.4.1.2 Cooling mode
In Cooling mode, the appliance cools the water when the sensor temperature is higher than the setpoint temperature
increased by the temperature dierenal (parameter F15). The appliance stops cooling the water when the temperature
is lower than the setpoint temperature reduced by the temperature dierenal (see following sequences.)