27
ALARMS AND CALIBRATION
F59
Minimum ambient temperature for
switching on the electrical resistance (in
°C)
-10 - 20 5
F60
Maximum temperature dierence
between water inlet and outlet
temperature (in °C)
0 - 20 4
F63
Calibraon of the defrosng temperature
sensor 1 (in °C)
-20 - 20 0
F64
Calibraon of the defrosng temperature
sensor 2 (in °C)
-20 - 20 0
F65
Calibraon of the ambient temperature
sensor (in °C)
-20 - 20 0
F66
Calibraon of the compressor 1 discharge
temperature sensor (in °C)
-20 - 20 0
F67
Calibraon of the compressor 2 discharge
temperature sensor (in °C)
-20 - 20 0
F68
Calibraon of the compressor 1 sucon
sensor (in °C)
-20 - 20 0
F69
Calibraon of the compressor 2 sucon
sensor (in °C)
-20 - 20 0
ELECTRONIC EXPANSION VALVE
F70
Electronic expansion valve
0: deacvated
1: acvated
0
F71
Refrigerant gas
0: R-410-A
1: R-407-C
0
F72
Maximum output voltage (V) 0.5 - 5.0 4.5
F73
Maximum sensor pressure (MPa) 0 - 5 4.6
F74
Inial posion of the valve in Cooling
mode (step)
100 - 480 240
F75
Inial posion of the valve in Heang
mode (step)
100 - 480 240
F76
Overheang adjustment me 0 - 120 30
F77
Step seng (ne) 0 - 10 1
F78
Step seng (average) 0 - 10 3
F79
Step seng (rough) 0 - 10 6
F80
Overheang in Heang mode (°C) 3 - 20 6
F81
Overheang in Cooling mode (°C) 3 - 25 10
F82
Maximum authorised evaporaon
temperature (°C)
10 -100 20
F83
High evaporaon temperature (°C) 1 - 5 2
F84
High evaporaon temperature delay (min) 1 - 3 2
SYSTEM
SETTINGS
F86
Test me
0 - 999
OFF: no test me
OFF
F87
Reset total operang me
YES
NO
NO
F88
Reset factory sengs
YES
NO
NO
APPLIANCE
INFORMATION
F90
Show the board model
F91
Show the board's soware version
F92
Show the screen model
F93
Show the screen soware version
F96
Set the me
F00
Exit
EN