26
DEFROSTING
F31
Start defrosng temperature (in °C) -10 - 0 -7
F32
Stop defrosng temperature (en °C) 5 - 35 15
F33
Start defrosng duraon (min) 1 -120 25
F34
Maximum defrosng duraon (min) 3 - 20 10
F35
Default temperature start defrosng (in
°C)
-10 - 20 7
F36
Alarm delay me aer defrosng 0 - 120 3
F37
4-way valve mode
0: OFF
1: ON
0
CONTROL
F38
Remote Cooling mode
0: setpoint not considered
1: setpoint considered
1
F39
Remote Heang mode
0: setpoint not considered
1: setpoint considered
1
ELECTRICAL CONNECTIONS
F40
Thermal protecon (A)
0 - 40
0: not acve
Depending on
model
TD35: 20
TD45: 26
TD60: 34
TD90: 26
TD120: 34
F42
Current(s) delay me 0 - 30 3
F44
% of phase(s) current imbalance 5 - 50 20
F45
Delay me of the absence of phase(s)
alarm
0 - 60 3
F46
Delay me of the phase(s) imbalance
alarm
0 - 30 2
F47
Delay me of the phase(s) fault alarm 0 - 30 2
F49
Autostart funcon (appliance
automacally resets following a power
cut)
0: deacvated
1: acvated
1
F50
Heang Priority
0: pump deacvated
1: pump acvated
(voltage 220 V)
1
FILTER PUMP
F51
Filtraon pump start-up delay before
compressor start-up (min)
1 - 10 3
F52
Filtraon pump stop-delay aer
compressor stop (min)
0 - 10 3
F53
Water temperature check interval (min) 0 - 99 60
F54
Filtraon pump operang me (min) 0 -99 5
F55
Compressor discharge temperature
protecon
90 - 135 115
F56
Water ow detector
0: deacvated
1: acvated
1
F57
Fan thermal relay
0: deacvated
1: acvated
1