5.4.3 I Operang principles of electrical protecon
5.4.3.1 Protecon system
The compressor's me delay is congurable (see § “5.3 I Advanced seng parameters (accessible by a qualied
technician)”, seng F21). This delay is used by the regulator to avoid connuous ON/OFF cycles. When the compressor
stops following an operang phase, the regulator checks that this me has elapsed before it restarts the compressor. If
not, the compressor can only restart aer 5 minutes. This 5 minute period must also elapse before the compressor can
start up when the equipment has just been started.
5.4.3.2 Remote switch
When the remote switch is closed, the switched-o appliance remains switched-o and the running appliance connues
to operate normally. When the remote switch is open, the switched-o appliance remains switched-o and the running
device stops. "OFF" is then displayed on the screen.
5.5 I Wiring diagrams
Wiring diagrams are available at the end of the document see §
5.5 Schémas électriques / Wiring diagrams /
Schaltplan / Elektrischschema / Esquema eléctrico / Esquema eléctrico / Schema elerico.