EasyManua.ls Logo

ZONEMASTER MAXIPOINT V2 - Turbo Group Functionality

ZONEMASTER MAXIPOINT V2
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ZONEMASTER MAXIPOINT V2 DAMPER CONTROL SYSTEM - Installation Manual
14
The factory default is set in spill mode and the
set-pointis30%.Whenthesetpointisreached
forspill,thescreenshows‘SPILLCONTROL’
and some of the lower order zones remain open
and will not respond to ON/OFF operation.
Similarly if bypass set point is reached the
screendisplays‘BYPASSCONTROL’asshown
intherightgure.
a) Atthesettingmodein‘Parameter’screen,
press or button to select
‘SafetySpill’.
b) Press button to select Spill or
Bypass mode.
c) Press or button to change
thespill/bypassset-pointtorequired
value.Theadjustablerangeisfrom0%
to50%with10%increments.
IMPORTANT: DO NOT set spill/bypass set-point to 0% unless there is
apermanentopenzoneusedasspillzone.Otherwise,therewillbe
no spill zone when all zones are closed and damage may be caused
byhighpressurebuildupinsideductsifairconditionerisrunning.
5) Turbo Group
The Turbo function will give the selected group
afull-openingwhilealltheothergroups
(dampers) opening positions are reduced by
50%oftheirbalancedvalue.Thiswillbringa
large volume of extra air into the designated
area and cool or heat the area quicker. Typically
thismaybeafamily-room,diningroomorhome
theatre (or in commercial application a meeting,
lunch or board room). (See Grouping Zones
section for how to group).