76VCCX2 Controller Technical Guide
APPENDIX C: BACNET GUIDE
Analog Inputs
VCCX2 ANALOG INPUTS
Parameter Object Description Limits
Alarm Status AI: 144 Indicates an alarm condition 0 = No Alarms,
1 = Alarm(s) Present
Outdoor Enthalpy AI: 145 Current Outdoor Enthalpy
Plenum Pressure AI: 146 Reserved
Return Fan Speed AI: 147 Reserved
Plenum Calculated Setpoint AI: 148 Reserved
Return Air Enthalpy Status AI: 149 Current value of Return Air Enthalpy
Current Duct Static Setpoint AI: 150 Status of the duct static setpoint
RSMZ 1 Condenser Fan AI: 151 Current RSMZ 1 condenser fan signal
RSMZ 1 VFD Comp Perc AI: 152 Current RSMZ 1 VFD Compressor Percentage
RSMZ 1 Discharge Pressure AI: 153 Current RSMZ 1 discharge pressure
RSMZ 1 Suction Pressure AI: 154 Current RSMZ 1 Suction Pressure
RSMZ 1 Suction Line Temp AI: 155 Current RSMZ 1 Suction Line Temperature
RSMZ 1 Saturation Temp AI: 156 Current RSMZ 1 Saturation Temperature
RSMZ 1 Superheat AI: 157 Current RSMZ 1 Superheat Temperature
RSMZ 1 EEV Position AI: 158 Current RSMZ 1 EEV Valve Position
RSMZ 1 Warnings AI: 159 Current RSMZ 1 Warnings See RSMZ Warnings Bits on page 91.
RSMZ 1 Comp VFD Alarms 1 AI: 160 Current RSMZ 1 Comp VFD Alarms 1 See RSMZ Alarms 1 Bits on page 92.
RSMZ 1 Comp VFD Alarms 2 AI: 161 Current RSMZ 1 Comp VFD Alarms 2 See RSMZ Alarms 2 Bits on page 92.
RSMZ 1 Comp VFD Drive
Status
AI: 162 Current RSMZ 1 Comp VFD drive status See RSMZ Drive Status Bits page 91.
RSMZ 1 Compressor Current AI: 163 Current reading in Amps that the RSMZ 1 compressor is
using
RSMZ 1 Discharge Line Temp AI: 164 Current RSMZ 1 discharge line temperature
RSMZ 1 Faults AI: 165 Current RSMZ 1 Faults See RSMZ Faults Bits on page 91.
RSMZ 1 Lockouts AI: 166 Current RSMZ 1 Lockouts See RSMZ Lockouts Bits on page 91.
RSMZ 2 Condenser Fan AI: 167 Current RSMZ 2 condenser fan signal
RSMZ 2 VFD Comp Perc AI: 168 Current RSMZ 2 VFD Compressor Percentage
RSMZ 2 Discharge Pressure AI: 169 Current RSMZ 2 discharge pressure
RSMZ 2 Suction Pressure AI: 170 Current RSMZ 2 Suction Pressure
RSMZ 2 Suction Line Temp AI: 171 Current RSMZ 2 Suction Line Temperature
RSMZ 2 Saturation Temp AI: 172 Current RSMZ 2 Saturation Temperature
RSMZ 2 Superheat AI: 173 Current RSMZ 2 Superheat temperature
RSMZ 2 EEV Position AI: 174 Current RSMZ 2 EEV valve position
RSMZ 2 Warnings AI: 175 Current RSMZ 2 Warnings See RSMZ Warnings Bits on page 91.
RSMZ 2 Comp VFD Alarms 1 AI: 176 Current RSMZ 2 Comp VFD Alarms 1 See RSMZ Alarms 1 Bits on page 92.
RSMZ 2 Comp VFD Alarms 2 AI: 177 Current RSMZ 2 Comp VFD Alarms 2 See RSMZ Alarms 2 Bits on page 92.
RSMZ 2 Comp VFD Drive
Status
AI: 178 Current RSMZ 2 Comp VFD drive status See RSMZ Drive Status Bits on page 91.
RSMZ 2 Compressor Current AI: 179 Current reading in Amps that the RSMZ 2 compressor is
using
RSMZ 2 Discharge Line Temp AI: 180 Current RSMZ 2 discharge line temperature
RSMZ 2 Faults AI: 181 Current RSMZ 2 Faults See RSMZ Faults Bits on page 91.
RSMZ 2 Lockouts AI: 182 Current RSMZ 2 Lockouts See RSMZ Lockouts Bits on page 91.
RSMZ 3 Condenser Fan AI: 183 Current RSMZ 3 condenser fan signal
Objects labeled AI are read-only.