Appendix C MODBUS® register lists
266 MODBUS® multivariable transmitter User manual 2105216 Rev. AB | 93
* Means these are ROM constant defaults and a read will always return these values.
Differential Pressure units select code
1 inch of water at 60 °F (ROM default)
2 Pascal
3 Kilopascals
6 inches of water at 68 °F
Static Pressure units select code
3 Kilopascal
4 Megapascal
5 PSIA (ROM default)
Temperature units select code
20 Degree Celsius
21 Degree Fahrenheit (ROM default)
Modbus turn-around response delay (ms per count)
† Value selected using HMI must equal one of these specific measurement units, or a NAK will be returned.
Differential Pressure (Damping, Calibration and Units applied) floating point, 401 is
high word, 402 is low word.
Static Pressure (Damping, Calibration and Units applied) floating point, 401 is high
word, 402 is low word.
Process Temperature (Damping, Calibration and Units applied) floating point, 401 is
high word, 402 is low word.
This may be external RTD or sensor value depending on configuration.
Diagnostics Status Word 1 and 2
Diagnostics Status Word 3 and 4
Diagnostics Status Word 5 and 6
DP URL, Upper Range Limit (Set by Measurement Sensor)
DP LRL, Lower Range Limit (Set by Measurement Sensor)
DP URV, Operating Upper Range Value (default URL)
DP LRV, Operating Lower Range Value (default LRL)
SP URL, Upper Range Limit (Set by Measurement Sensor)
SP LRL, Lower Range Limit (Set by Measurement Sensor)
SP URV, Operating Upper Limit (default SP URL)
SP LRV, Operating Lower Limit (default SP LRL)
T URL, Upper Range Limit (default 850ºC)
T LRL, Lower Range Limit(default -200ºC)
T URV, Operating Upper Range Value (default URL)
T LRV, Operating Lower Range Value (default LRL)
DP offset calibration value (default 0.0)
DP span calibration value ( default URL)
SP offset calibration value (default 0.0)
SP span calibration value ( default URL)
T offset calibration value (default 0.0)
T span calibration value (default URL)
T dampening (default 0.0)