Appendix C MODBUS® register lists
92 | 266 MODBUS® multivariable transmitter User manual 2105216 Rev. AB
C.2 Rosemount 3095FB emulation register map
Table 21: Rosemont MODBUS
®
register map
Register Address
Type
*Constant /
Default
Object description
32 bit
16 bit
7001
1
U8
*0
Manufacturer’s Code Rosemount
7002
2
U8
*31
Transmitter Type Code Multivariable Transmitter with Modbus
7003
3
U8+U8
*0x6803
Output Board Software Rev Level (rev 104.3)
7004
4
U8
*4
Sensor Module Software Rev Level
7005-
7006
5 & 6
U24
Device serial Number made from the 32 byte transducer number.
The number is made from the last 6 decimal digits in the string.
See (ABB map register 0001-0008)
Ex. “T123456789001”
Reg 5&6 read as 32bit integer is 789001
Reg 5 read as 16bit integer is 0x000C
Reg 6 read as 16bit integer is 0x0A09
7007-
7008
7 & 8
U24
Same information as 7005-7006.
7009
09
U8
*0
Hardware Rev Level
7010
10
U8
*16
Modbus Specific Rev Level
7011
11
U8
*23
Sensor Type absolute SP
7012
12
U8
*1
reserved
7013
13
U8
*0
Reserved
7014
14
U8
*0
Reserved
7015
15
U8
8
Baud rate selector
1 = 1200, 2 = 2400, 3 = 4800, 4 = 9600, 5 = 1200,
6 = 2400, 7 = 4800, 8 = 9600, 9 = 19200
7016
16
U8
247
Modbus Transmitter address
7017
17
U8
*252
DP Sensor Range Code (unknown code)
7018
18
U8
*252
SP Sensor Range Code
7019
19
U8
*252
PT Sensor Range Code
7020
20
U8
*252
Module Isolator Code
7021
21
U8
*252
Module Fill Fluid Code
7022
22
U8
*252
flange material code
7023
26
U8
*252
flange type code
7024
24
U8
*252
drain/vent code
7025
25
U8
*252
O-ring gasket material
7026
26
U8
*252
remote seal type
7027
27
U8
*252
remote seal fill fluid
7028
28
U8
*252
remote seal isolator material
7029
29
U8
*252
number of remote seals
7030 7031
30 31
U32
*0
N/A
7032 7041
32 41
U8 string
Read/Write
user-entered tag, user-entered descriptor, 20 char
7042 7056
42 56
U8 string
Read
Nonvolatile memory page 30 bytes
7057
57
U8
*0
N/A
7058
58
U8
*0
N/A
7059
59
U8
*0
N/A