EasyManua.ls Logo

ABB 266 MODBUS - 3.6 Electrical connections

ABB 266 MODBUS
164 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 Installation
28 | 266 MODBUS® multivariable transmitter User manual 2105216 Rev. AB
Electrical connections
Protective conductor and grounding
A terminal is available on the transmitter exterior for connection to an earth ground or potential equalization (PE) grid (Figure
24). A connection for attaching wiring shields is located inside of the rear housing cover. For additional field wiring requirements
see the following publications:
For European applications, see Standards IEC60364 and IEC60079-14 for installation of electrical equipment.
For United States or Canada Division or Zone rated applications, see NEC (NFPA 70) section 500 or CSA C22.1.
Figure 24: Ground connections
In order to fulfill the requirements of the low-voltage guidelines and the relevant EN 61010 rules for the installation of electrical
equipment, the housing must be provided with a protective circuit (for example: grounding or protective conductor) if voltages
greater than 150 Vdc could occur.
Integrated surge protector
The 266 MODBUS
®
transmitter terminal block includes transient suppression circuitry built in. The circuitry is based on a four-
tier protection design that protects the power inputs and communications.
For correct operation of the suppression system a high-current path to earth ground or potential equalization (PE) grid is
required (Figure 24). Section 3.6.1, Protective conductor and grounding, includes additional information on grounding the
transmitter.
IMPORTANT NOTE: The grounding (PE) should be kept as short as possible with a minimum wire size of 12
AWG.

Table of Contents

Related product manuals