EasyManua.ls Logo

ABB 266 MODBUS - Figure 26: RTD Simulation Wiring

ABB 266 MODBUS
164 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 Installation
266 MODBUS® multivariable transmitter User manual 2105216 Rev. AB | 31
3. If a live temperature sensor (RTD) is installed in the meter run, remove the jumpers and resistor from the RTD terminals on
the termination block. Otherwise, continue to step 5.
a. Using a small phillips screwdriver, loosen the terminal 2 and 3 screws (Figure 26) and remove resistor.
RTD Simulation:
178 Ω resistor with
2 jumper wires
Figure 26: RTD Simulation wiring
b. Loosen the terminal 1 screw and remove the jumper wire.
c. Loosen the terminal 4 screw and remove the jumper wire.
IMPORTANT NOTE: For the purpose of temperature simulation, a 178 Ω resistor (206 °C / 402.8 °F) with 2
jumpers has been installed between the terminals for the temperature RTD connection. This resistor (including
the jumpers in the case of 4-wire connections) must be removed before connecting the RTD. If a temperature
RTD is not connected, the resistor must remain in place. If an RTD is installed, the 178 Ω resistor removed
from the RTD terminals may be used as an RS- 485 Bus termination.

Table of Contents

Related product manuals