2 System description
12 | 266 MODBUS® multivariable transmitter User manual 2105216 Rev. AB
MODBUS
®
communication can be configured to emulate three different transmitter register maps:
— ABB transmitter 267/269 (Default)
— Rosemount 3095FB
— Invensys IMV25
Go to Appendix C, MODBUS
®
register lists for detailed MODBUS
®
register tables.
Mapping tables assign 16 bit system objects to 32 bit register addresses. This allows the MODBUS
®
Master to select and use a
single addressing mode. The MODBUS
®
processor zero-fills any undefined 16 bit objects. The defined bits occupy the LSB
(least significant (lower) bits) and the zeroed bits are the MSB (most significant (higher) bits). A 32 bit register address is
mapped the same way as a single 16 bit register address. MODBUS
®
communication prevents a protected register object from
being overwritten.