Figure 3.11: Firmware Update Page
Do not disconnect the power from the Linking Device while firmware download or
reboot are in progress. Wait at least 60 seconds after the Success message has
shown up.
This subsection explains the general mechanism of updating the firmware of a Linking
Device. Updating the firmware in a redundant set of Linking Devices requires special
procedures described in section Firmware Update for a Redundant Set of Linking
Devices on page 67.
Firmware Update for a Non-Redundant Set of Linking Devices.
Updating the firmware of a non-redundant Linking Device requires the plant to be
shut down.
During the firmware update process, a caution note is displayed for the user to change
the default password for accessing the Linking Device.
1. Click the Browse button on the Firmware Update page to open a file selector box.
2. Select the firmware file to be downloaded.