5. Wait until the successful completion of the update process is indicated by a Success
message, see Figure 3.12.
After the Success message is displayed, do not power down the Linking Device before
the H1 link LEDs have lit up at least once or at least 60 seconds have elapsed.
Figure 3.12: Page After Successful Firmware Update
The end of the boot process is indicated by a continuously lit RUN LED for a
LD 810HSE Ex acting in non-redundant mode or for a primary device in redundant
mode. For a secondary device it is indicated by a flashing (1 Hz) RUN LED.
6. Click Default Values to reset changes made to this page so that the check box is
deactivated and no firmware file is selected.
7. If the Linking Device configuration was erased, download the configuration data to
the Linking Device.
Downloading configuration data to a Linking Device requires two steps to be carried
out in the ABB configuration tools:
• initialization and address assignment of the Linking Device
• and download of the Linking Device
It is not required to re-assign or load H1 devices after a firmware update of a
Linking Device.
Firmware Update for a Redundant Set of Linking Devices. Apply one of the following
procedures for updating the firmware in a redundant set of Linking Devices. If the
configuration file format is the same for the old and new firmware release, it is
recommended to execute the procedure given in Identical Configuration File Formats
on page 68, as this will minimize the impact on process operation. In the case of different
or unknown configuration file formats, execute the steps described in Different or Unknown
Configuration File Formats on page 68.
2PAA114135-610 67
3 Configuration
3.2 System Settings