66 ACS 300 User’s Manual
Chapter 7 - Drive Parameters
9 (Under Panel Control (LOCAL state))
Relay is de-energised while the LOCAL state is active
(REMOTE LED on the panel is not illuminated).
10 (None)
Relay is de-energised.
Note! Relay is de-energised, if this function is selected while
the relay is energised.
11 (Fault (-1))
Relay is energised (and the fault LED on the Control Panel
illuminates), when a fault is active.
Note! When planning the application of the programmable
relay, do not forget that the relay is always de-energised
when the drive power is shut off.
F SUPERV
F SUPERV is the frequency limit for relay functions 4 and 5.
Please look at the previous parameter.
Page 3 parameters
PAGE 3 (*P4)
Press
to change to Page 4.
DC HOLD
This parameter enables the DC HOLD feature. There are
three options for using this parameter.
0 (Off)
DC HOLD is disabled.
1 (Normal)
This option provides “less” DC current and hold torque to the
motor than option 2. We recommend that you try this option
first to see if you can get enough hold.
2 (Strong)
This option provides adequate DC current and hold torque
to the motor.