68 ACS 300 User’s Manual
Chapter 7 - Drive Parameters
PI-GAIN
This parameter defines the gain of PI Controller. The setting
range is 0 to 800 %. If the value is 0 %, the PI Controller is
inactive. Changing of PI-GAIN from 0 is possible only when
start is inactive. The following table shows how the output
frequency changes to a 10 % change in error and a 50 %
change in error with different gain selections.
Some points of view must be taken in consideration when
this parameter is active:
The Local Ref parameter is not displayed.
The analog input, AI is used only as the actual value (pro-
cess feedback) input. PI-REF is changed through the con-
trol panel when the drive is in the local mode and as
described below when the drive is in the remote mode.
The texts on the control panel display for constant fre-
quencies will be CR1, CR2 and CR3. CR = Constant Ref-
erence. The unit is %. With these parameters you can
give constant reference values in the remote mode.
Joystick control does not operate. On the other hand PI
Control cannot be selected while Joystick control is active.
Custom settings have no effect.
The rotation direction cannot be changed.
Critical frequency ranges are ignored.
PI-ITIME
Defines the integral time of PI Controller. The setting range
is 0.0 to 320.0 s. PI Controller operates as a P Controller
when the parameter value is 320.0 s.
PI-GAIN
Output frequency change
for a 10 % change in error
Output frequency change for a
50 % change in error
50 % 0.75 Hz 3.75 Hz
100 % 1.5 Hz 7.5 Hz
300 % 4.5 Hz 22.5 Hz