76 ACS 300 User’s Manual
Chapter 8 - Fault Tracing
(5) LOW AI-SIGNAL Analogue input less than 2 V/
4mA and minimum has been
set to
2 V/4 mA or Analogue Input
less than selected “customized
minimum”.
Input reference has failed or
control wire is broken. Check
the reference circuit.
(6) PANEL COM ERR Control Panel was removed
when control was in Local
mode. Due to safety reasons,
the drive stops in this fault con-
dition.
Attach the Control Panel and
reset the fault, then change to
Remote mode and remove
Panel.
Use remote (wired) controls to
reset the fault, then start and
run with remote controls
There might be a loose con-
tact. Check the panel connec-
tion.
(10) BUS COMM FLT Bus communication error Check bus connections
(7) UNIT FAULT ACS 300 heatsink tempera-
ture too high.
CHECK:
Heatsink dissipation
Dust and dirt
Air flow
•Fan
Ambient temperature
Reduce switching frequency.
Check load current
Ground faults or short circuits. CHECK:
Terminals
Motor
Wiring
With frame size R2 high load
inertia / short ramp
CHECK:
Ramps times
Remove mechanical problems
Dimensioning
Fault indication Possible cause Remedy