88 ACS 300 User’s Manual
Appendix A - Product Conformity in EEA
between the clamp and the screw terminals as short as pos-
sible. Route the mains wires away from the others.
Connect the mains and motor cables according to the layout
in Figure 3-1 on page 18.
In case the shield is used also as a protective conductor,
you must connect it both to the clamp and to the PE termi-
nal. Clamping alone is insufficient.
Note! In addition to clamping the motor cable screen to the
clamping plate at the ACS 300, connect the screen to motor
earth at the motor.
Clamp the control cable at the entry point, see Figure A-3
and Figure A-4. Make it certain that the screen of the cable
makes a solid contact to both parts of the clamp. Leave the
individual unscreened wire loops between the clamp and the
screw terminals as short as possible. Route the control
cable away from the motor cable. Control cables must be
multi-core cables with braid shield.