Drive module of frame size R7 with bottom exit
20
Cable lead-through plates
EMC kit 64331116 contains the lead-throughs without the strain relief plates shown
below.
EMC sleeve
Lead-through plate
Strip this part
of the cable
Cable shield
Base plate
PE terminal
Grommet
Installing the power cables
Entries for power cables (conductive sleeves inside
the grommets). Cut an adequate hole to the rubber
grommet. Lead the cable through the grommet and the
conductive sleeve as shown below.
In first environment installations, 360 degrees
grounding must be applied to motor cables and is also
recommended for input cables.
Recommended entry for control
cables in first environment
installations (360 degrees grounding
between the conductive cushions)
Note: Control cable lead-throughs
with rubber grommets only may also
be possible.
Grommet
EMI conductive
Lead-through
cushion
plate
Strain
relief