Planning the cabinet installation
25
Layout examples, door open
WARNING! For units without bottom exit kit (+H352), it is not allowed to connect the
cables directly to the drive module terminals without the pedestal as the lead-
through insulation material is not strong enough to carry the mechanical stress
exerted by the cables.
n
n
1 Supporting frame of the cabinet
2 Air baffles that separate the cool and hot
areas (leak-proof lead-throughs)
3 Input power cable including the protective
conductors to cabinet grounding (PE)
4 Disconnector and fuses
5 Contactor
6 Converter module
7 Motor cable including the grounding
conductors
8 Drive Control Unit RDCU (includes RMIO
board)
9 External control cables
5
8
3
PE
9
4
6
3
3
3
7
2
1
IP 54
n
n
5
8
3
PE
9
4
6
3
3
3
7
2
1
IP 22
2
2
Air flow to the roof
Fan
IP 54
IP 22
Air flow through the module
See also section Required free space around the drive
module for cooling.