Start-up and use 29
4
Start-up and use
Contents of this chapter
This chapter contains the start-up and acceptance test procedure for the Safe torque off
function and gives instructions for its use.
Start-up and acceptance test
To ensure the safe operation of a safety function, validation is required. The final
assembler of the machine must validate the function by performing an acceptance test.
The acceptance test must be performed
at initial start-up of the safety function
after any changes related to the safety function (circuit boards, wiring, components,
settings, etc.)
after any maintenance work related to the safety function.
Competence
The acceptance test of the safety function must be carried out by a competent person with
adequate expertise and knowledge of the safety function as well as functional safety, as
required by IEC 61508-1 clause 6. The test procedures and report must be documented
and signed by this person.