Parameters 183
50.05 Fba ref2 modesel Selects the fieldbus reference FBA REF2 scaling.
See parameter 50.04 Fba ref1 modesel.
Raw data See parameter 50.04 Fba ref1 modesel.0
Torque See parameter 50.04 Fba ref1 modesel.1
Speed See parameter 50.04 Fba ref1 modesel.2
50.06 Fba act1 tr src Selects the source for fieldbus actual value 1 when parameter
50.04 Fba ref1 modesel / 50.05 Fba ref2 modesel is set to
Raw data.
Pointer Value pointer setting (see Terms and abbreviations on page
63).
-
50.07 Fba act2 tr src Selects the source for fieldbus actual value 2 when parameter
50.04 Fba ref1 modesel / 50.05 Fba ref2 modesel is set to
Raw data.
Pointer Value pointer setting (see Terms and abbreviations on page
63).
-
50.08 Fba sw b12 src Selects the source for freely programmable fieldbus status
word bit 28 (02.24 FBA main sw bit 28 SW B28).
Const Bit pointer setting (see Terms and abbreviations on page 63). -
Pointer
50.09 Fba sw b13 src Selects the source for freely programmable fieldbus status
word bit 29 (02.24 FBA main sw bit 29 SW B29).
Const Bit pointer setting (see Terms and abbreviations on page 63). -
Pointer
50.10 Fba sw b14 src Selects the source for freely programmable fieldbus status
word bit 30 (02.24 FBA main sw bit 30 SW B30).
Const Bit pointer setting (see Terms and abbreviations on page 63). -
Pointer
50.11 Fba sw b15 src Selects the source for freely programmable fieldbus status
word bit 31 (02.24 FBA main sw bit 31 SW B31).
Const Bit pointer setting (see Terms and abbreviations on page 63
). -
Pointer
51
51 FBA settings
Fieldbus adapter-specific settings.
51.01 FBA type Displays the type of the connected fieldbus adapter module.
0 = Fieldbus module is not found, or it is not properly
connected, or parameter 50.01 Fba enable is set to Disable,
1 = FPBA-xx PROFIBUS-DP adapter module, 32 = FCAN-xx
CANopen adapter module, 37 = FDNA-xx DeviceNet adapter
module
51.02 FBA par2 Parameters 51.02…51.26 are adapter module-specific. For
more information, see the User’s Manual of the fieldbus
adapter module. Note that not all of these parameters are
necessarily visible.
-
…… … …
51.26 FBA par26 See parameter 51.02 FBA par2.-
No. Name/Value Description FbEq