154   Parameters
Pointer Value pointer setting (see Terms and abbreviations on page 
63).
-
33.11 Superv3 hi Selects the upper limit for supervision 3. See parameter 33.09 
Superv3 func.
-32768.00 … 
32768.00
Upper limit for supervision 3. 100 = 1
33.12 Superv3 lo Selects the lower limit for supervision 3. See parameter 33.09 
Superv3 func.
-32768.00 … 
32768.00
Lower limit for supervision 3. 100 = 1
34
34 User load curve
Definition of user load curve. See also section User load 
curve on page 50.
34.01 Overload func Configures the supervision of the upper boundary of the user 
load curve.
No. Name/Value Description FbEq
Bit Function
0 Ena sup (Enable supervision)
0 = Disabled: Supervision disabled.
1 = Enabled: Supervision enabled.
1 Input value sel (Input value selection)
0 = Current: Current is supervised.
1 = Torque: Torque is supervised.
2 Ena warn (Enable warning)
0 = Disabled
1 = Enabled: Drive generates an alarm when the curve is exceeded.
3 Ena fault (Enable fault)
0 = Disabled
1 = Enabled: Drive trips on a fault when the curve is exceeded.
4 Ena lim integ (Enable limit integration)
0 = Disabled
1 = Enabled: Integration time defined by parameter 34.18 Load integ time is used. After 
the supervision is evoked, the current or torque is limited by the upper boundary of the 
load curve.
5 Ena lim always (Enable limit always)
0 = Disabled
1 = Enabled: The current or torque is always limited by the upper boundary of the load 
curve.