Parameters 181
0.0000 …
10000.0000 kW
Maximum continuous braking power. 10000 =
1kW
48.05 R br Defines the resistance value of the brake resistor. The value
is used for brake chopper protection.
0.1000 …
1000.0000 ohm
Brake resistor resistance value. 10000 =
1 ohm
48.06 Br temp faultlim Selects the fault limit for the brake resistor temperature
supervision. The value is given in percent of the temperature
the resistor reaches when loaded with the power defined by
parameter 48.04 Br power max cnt.
When the limit is exceeded the drive trips on fault BR
OVERHEAT.
0 … 150% Brake resistor temperature fault limit. 1 = 1%
48.07 Br temp alarmlim Selects the alarm limit for the brake resistor temperature
supervision. The value is given in percent of the temperature
the resistor reaches when loaded with the power defined by
parameter 48.04 Br power max cnt.
When the limit is exceeded, the drive generates a BR
OVERHEAT alarm.
0 … 150% Brake resistor temperature alarm limit. 1 = 1%
49
49 Data storage
Data storage parameters reserved for the user. These
parameters can be written to and read from using other
parameters’ pointer settings.
Four 16-bit and four 32-bit storage parameters are available.
49.01 Data storage1 Data storage parameter 1.
-32768 … 32767 16-bit data. 1 = 1
49.02 Data storage2 Data storage parameter 2.
-32768 … 32767 16-bit data. 1 = 1
49.03 Data storage3 Data storage parameter 3.
-32768 … 32767 16-bit data. 1 = 1
49.04 Data storage4 Data storage parameter 4.
-32768 … 32767 16-bit data. 1 = 1
49.05 Data storage5 Data storage parameter 5.
-2147483647 …
2147483647
32-bit data. 1 = 1
49.06 Data storage6 Data storage parameter 6.
-2147483647 …
2147483647
32-bit data. 1 = 1
49.07 Data storage7 Data storage parameter 7.
-2147483647 …
2147483647
32-bit data. 1 = 1
49.08 Data storage8 Data storage parameter 8.
-2147483647 …
2147483647
32-bit data. 1 = 1