EasyManua.ls Logo

ABB ACS850 - Automatic Reset; Supervision

ABB ACS850
260 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters 151
32
32 Automatic reset
Defines conditions for automatic fault resets.
32.01 Autoreset sel Selects faults that are automatically reset. The parameter is a
16-bit word with each bit corresponding to a fault type.
Whenever a bit is set to 1, the corresponding fault is
automatically reset.
The bits of the binary number correspond to the following
faults:
32.02 Number of trials Defines the number of automatic fault resets the drive
performs within the time defined by parameter 32.03 Trial
time.
0 … 5 Number of automatic resets. 1 = 1
32.03 Trial time Defines the time for the automatic fault reset function. See
parameter 32.02 Number of trials.
1.0 … 600.0 s Time for automatic resets. 10 = 1 s
32.04 Delay time Defines the time that the drive will wait after a fault before
attempting an automatic reset. See parameter 32.01
Autoreset sel.
0.0 … 120.0 s Resetting delay. 10 = 1 s
33
33 Supervision
Configuration of signal supervision.
33.01 Superv1 func Selects the mode of supervision 1.
Disabled Supervision 1 not in use. 0
Low When the signal selected by parameter 33.02 Superv1 act
falls below the value of parameter 33.04 Superv1 lo, bit 0 of
06.13 Superv status is activated.
1
High When the signal selected by parameter 33.02 Superv1 act
exceeds the value of parameter 33.03 Superv1 hi, bit 0 of
06.13 Superv status is activated.
2
Abs Low When the absolute value of the signal selected by parameter
33.02 Superv1 act falls below the value of parameter 33.04
Superv1 lo, bit 0 of 06.13 Superv status is activated.
3
Abs High When the absolute value of the signal selected by parameter
33.02 Superv1 act exceeds the value of parameter 33.03
Superv1 hi, bit 0 of 06.13 Superv status is activated.
4
33.02 Superv1 act Selects the signal to be monitored by supervision 1. See
parameter 33.01 Superv1 func.
Speed rpm 01.01 Motor speed rpm (see page 64). 1073742081
Speed % 01.02 Motor speed % (see page 64). 1073742082
Frequency 01.03 Output frequency (see page 64). 1073742083
Current 01.04 Motor current (see page 64). 1073742084
Current % 01.05 Motor current % (see page 64). 1073742085
No. Name/Value Description FbEq
Bit Fault
0 Overcurrent
1 Overvoltage
2 Undervoltage
3AI min
4 Line converter
5 External fault

Table of Contents