Parameters 151
32
32 Automatic reset
Defines conditions for automatic fault resets.
32.01 Autoreset sel Selects faults that are automatically reset. The parameter is a
16-bit word with each bit corresponding to a fault type.
Whenever a bit is set to 1, the corresponding fault is
automatically reset.
The bits of the binary number correspond to the following
faults:
32.02 Number of trials Defines the number of automatic fault resets the drive
performs within the time defined by parameter 32.03 Trial
time.
0 … 5 Number of automatic resets. 1 = 1
32.03 Trial time Defines the time for the automatic fault reset function. See
parameter 32.02 Number of trials.
1.0 … 600.0 s Time for automatic resets. 10 = 1 s
32.04 Delay time Defines the time that the drive will wait after a fault before
attempting an automatic reset. See parameter 32.01
Autoreset sel.
0.0 … 120.0 s Resetting delay. 10 = 1 s
33
33 Supervision
Configuration of signal supervision.
33.01 Superv1 func Selects the mode of supervision 1.
Disabled Supervision 1 not in use. 0
Low When the signal selected by parameter 33.02 Superv1 act
falls below the value of parameter 33.04 Superv1 lo, bit 0 of
06.13 Superv status is activated.
1
High When the signal selected by parameter 33.02 Superv1 act
exceeds the value of parameter 33.03 Superv1 hi, bit 0 of
06.13 Superv status is activated.
2
Abs Low When the absolute value of the signal selected by parameter
33.02 Superv1 act falls below the value of parameter 33.04
Superv1 lo, bit 0 of 06.13 Superv status is activated.
3
Abs High When the absolute value of the signal selected by parameter
33.02 Superv1 act exceeds the value of parameter 33.03
Superv1 hi, bit 0 of 06.13 Superv status is activated.
4
33.02 Superv1 act Selects the signal to be monitored by supervision 1. See
parameter 33.01 Superv1 func.
Speed rpm 01.01 Motor speed rpm (see page 64). 1073742081
Speed % 01.02 Motor speed % (see page 64). 1073742082
Frequency 01.03 Output frequency (see page 64). 1073742083
Current 01.04 Motor current (see page 64). 1073742084
Current % 01.05 Motor current % (see page 64). 1073742085
No. Name/Value Description FbEq
Bit Fault
0 Overcurrent
1 Overvoltage
2 Undervoltage
3AI min
4 Line converter
5 External fault