Parameters 65
01.29 Torq nom scale Nominal torque which corresponds to 100%.
Note: This value is copied from parameter 99.12 Mot nom
torque if entered. Otherwise the value is calculated.
1000 =
1N•m
01.30 Polepairs Calculated number of pole pairs in the motor. 1 = 1
01.31 Mech time const Mechanical time constant of the drive and the machinery as
determined by the speed controller autotune function.
See parameter group 23 Speed ctrl on page 128.
1000 = 1 s
01.32 Temp phase A Measured temperature of phase U power stage in degrees
Celsius.
10 = 1 °C
01.33 Temp phase B Measured temperature of phase V power stage in degrees
Celsius.
10 = 1 °C
01.34 Temp phase C Measured temperature of phase W power stage in degrees
Celsius.
10 = 1 °C
01.35 Saved energy Energy saved in kWh compared to direct-on-line motor
connection.
See parameter group 45 Energy optimising on page 179.
1 = 1 kWh
01.36 Saved amount Monetary savings compared to direct-on-line motor
connection. This value is a multiplication of parameters 01.35
Saved energy and 45.02 Energy tariff1.
See parameter group 45 Energy optimising on page 179.
1 = 1
01.37 Saved CO2 Reduction in CO
2
emissions in metric tons compared to
direct-on-line motor connection. This value is a calculated by
multiplying saved energy in megawatt-hours by 0.5 metric
tons/MWh.
See parameter group 45 Energy optimising on page 179.
1 = 1 metric
ton
02
02 I/O values
Input and output signals.
02.01 DI status Status of digital inputs DI6…DI1. Example: 000001 = DI1 is
on, DI2…DI6 are off.
Note: If an FIO-21 extension is installed, the status of its
digital input is indicated by parameter 02.03 DIO status.
-
02.02 RO status Status of relay outputs RO5…RO1. Example: 00001 = RO1
is energized, RO2…RO5 are de-energized.
-
02.03 DIO status Status of digital input/outputs DIO10…DIO1. Example:
0000001001 = DIO1 and DIO4 are on, remainder are off.
Note: If an FIO-21 extension is installed, the status of its
digital input is also indicated by this parameter.
-
02.04 AI1 Value of analogue input AI1 in V or mA. Input type is selected
with jumper J1 on the JCU Control Unit.
1000 = 1 unit
02.05 AI1 scaled Scaled value of analogue input AI1. See parameters 13.04
AI1 max scale and 13.05 AI1 min scale.
1000 = 1 unit
02.06 AI2 Value of analogue input AI2 in V or mA. Input type is selected
with jumper J2 on the JCU Control Unit.
1000 = 1 unit
02.07 AI2 scaled Scaled value of analogue input AI2. See parameters 13.09
AI2 max scale and 13.10 AI2 min scale.
1000 = 1 unit
02.08 AI3 Value of analogue input AI3 in V or mA. For input type
information, see the extension module manual.
1000 = 1 unit
02.09 AI3 scaled Scaled value of analogue input AI3. See parameters 13.14
AI3 max scale and 13.15 AI3 min scale.
1000 = 1 unit
02.10 AI4 Value of analogue input AI4 in V or mA. For input type
information, see the extension module manual.
1000 = 1 unit
No. Name/Value Description FbEq