Program features 41
when the pressure falls under the predefined minimum level and the wake-up delay
has passed.
Settings
Parameter group 27 Process PID (page 139).
The PID control macro can be activated from the control panel main menu by
selecting ASSISTANTS – Firmware assistants – Application Macro – PID control. See
also page 56.
Programmable analog inputs
The drive has two programmable analog inputs. Each of the inputs can be
independently set as a voltage (0/2…10 V or -10…10 V) or current (0/4…20 mA)
input by a jumper on the JCU Control Unit. Each input can be filtered, inverted and
scaled. The number of analog inputs can be increased by using FIO-xx I/O
extensions.
t<t
d
t
d
SLEEP MODE
t
wd
t
wd
Motor Speed
t
d
= Sleep delay (27.24)
t
wd
= Wake-up delay (27.26)
Sleep level
(27.23)
STOP START
Actual value
Actual value
Wake-up level
(27.23)
Time
Time
Time
Wake-up level
(27.23)
Non-inverted (source of 27.23 = 0)
Inverted (source of 27.23 = 1)