CONTROLMASTER CM10 |  UNIVERSAL PROCESS CONTROLLER,  DIN  |  CI/CM10-EN REV. C
23
Icon Number/
Message
Possible cause Suggested action


Abnormal oscillations in the control loop. Check process.
Perform new manual or Autotune.


Sticking
Motorized valve travel time is significantly
slower than configured time.
Check valve to identify reason for sticking.
Check correct travel time is entered in configuration.





Autotune is in progress. Autotune can be aborted if required by selecting Manual control
mode.



Autotune has completed successfully and
calculated new control parameters.
Acknowledge diagnostic.

In
Configuration
The device is currently in the configuration
mode.