Digital inputs/outputs
2 optional, user programmable as input or output.
Minimum input pulse duration: 125 ms
Input
Volt free
24 V DC (1 signal 15 to 30 V, 0 signal -3 to 5 V)
Output
Open collector output
30 V, 100 mA max. switched
Conforms to IEC 61131-2
Update Rate
125 ms
Environmental data
Ambient operating temperature
0 to 55 °C (32 to 131 °F)
Ambient operating humidity
5 to 95 % RH non-condensing
Storage temperature
–20 to 70 °C (–4 to 158 °F)
Approvals, certification & general safety
EN-61010-1
cULus
Overvoltage class III on mains, Class II on
inputs and outputs
Pollution category 2
Insulation category 2
Emissions and Immunity
Meets the requirements of IEC 61326 for an industrial
environment