2.3 DCS 600 Overload Withstand Capability
To match a drive system’s components as efficiently as
possible to the driven machine’s load profile, the power
converters can be dimensioned by means of the load cycle.
Load cycles for driven machines have been defined in the
IEC 146 or IEEE specifications, for example.
The currents for the DC I to DC IV types of load (see diagram on the
following page) for the power converter modules are listed in the table
below.
Table 2.3/1: The power converter modules’ currents with the corresponding load cycles.
The characteristics are based on an ambient temperature of max. 40°C and an elevation
of max. 1000 meters.
II F 2-6
Unit type I
DC I
I
DC II
I
DC III
I
DC IV
contin- 100 % 150 % 100 % 150 % 100 % 200 %
uous 15 min 60 s 15 min 120 s 15 min 10 s
400 V / 500 V [A] [A] [A] [A]
DCS60x-0025-41 / 51 25 24 36 23 35 24 48
DCS60x-0050-41 / 51 50 44 66 42 63 40 80
DCS60x-0075-41 / 51 75 60 90 56 84 56 112
DCS60x-0100-41 / 51 100 71 107 69 104 68 136
DCS601-0140-41 / 51 125 94 141 91 137 90 180
DCS602-0140-41 / 51 140 106 159 101 152 101 202
DCS601-0200-41 / 51 180 133 200 132 198 110 220
DCS602-0200-41 / 51 200 149 224 146 219 124 248
DCS601-0250-41 / 51 225 158 237 155 233 130 260
DCS602-0250-41 / 51 250 177 266 173 260 147 294
DCS601-0350-41 / 51 315 240 360 233 350 210 420
DCS602-0350-41 / 51 350 267 401 258 387 233 466
DCS601-0450-41 / 51 405 317 476 306 459 283 566
DCS602-0450-41 / 51 450 352 528 340 510 315 630
DCS601-0520-41 / 51 470 359 539 347 521 321 642
DCS602-0520-41 / 51 520 398 597 385 578 356 712
DCS60x-0700-41 / 51 700 556 834 534 801 524 1048
DCS60x-0900-41 / 51 900 684 1026 670 1005 594 1188
DCS60x-1200-41 / 51 1200 888 1332 872 1308 764 1528
DCS60x-1500-41 / 51 1500 1200 1800 1156 1734 1104 2208
DCS60x-2000-41 / 51 2000 1479 2219 1421 2132 1361 2722
DCS60x-2500-41 / 51 2500 1830 2745 1740 2610 1725 3450
DCS60x-3300-41 / 51 3300 2416 3624 2300 3450 2277 4554
DCS60x-4000-41 / 51 4000 2977 4466 2855 4283 2795 5590
DCS60x-5150-41 / 51 5150 3800 5700 3669 5504 3733 7466
600 V / 690 V
DCS60x-0050- 61 50 44 66 43 65 40 80
DCS601-0110- 61 100 79 119 76 114 75 150
DCS602-0110- 61 110 87 130 83 125 82 165
DCS601-0270- 61 245 193 290 187 281 169 338
DCS602-0270- 61 270 213 320 207 311 187 374
DCS601-0450- 61 405 316 474 306 459 282 564
DCS602-0450- 61 450 352 528 340 510 313 626
DCS60x-0900-61 / 71 900 684 1026 670 1005 594 1188
DCS60x-1500-61 / 71 1500 1200 1800 1104 1656 1104 2208
DCS60x-2050-61 / 71 2050 1502 2253 1426 2139 1484 2968
DCS60x-2500-61 / 71 2500 1830 2745 1740 2610 1725 3450
DCS60x-3300-61 / 71 3300 2416 3624 2300 3450 2277 4554
DCS60x-4000-61 / 71 4000 3036 4554 2900 4350 2950 5900
DCS60x-4750-61 / 71 4750 3734 5601 3608 5412 3700 7400
790 V
DCS60x-2050-81 2050 1502 2253 1426 2139 1484 2968
DCS60x-3200-81 3200 2655 3983 2540 3810 2485 4970
DCS60x-4000-81 4000 3036 4554 2889 4334 2933 5866
DCS60x-4750-81 4750 3734 5601 3608 5412 3673 7346
1000 V
DCS60x-2050-91 2050 1577 2366 1500 2250 1471 2942
DCS60x-2650-91 2650 2000 3000 1900 2850 1922 3844
DCS60x-3200-91 3200 2551 3827 2428 3642 2458 4916
DCS60x-4000-91 4000 2975 4463 2878 4317 2918 5836
x=1 → 2-Q; x=2 → 4-Q
also available as field supply converter DCF60x with the appropriate voltage class marked. Data are
the same as the armature current converter DCS60x