Table 3.7/9: Digital outputs Armature converter mode (DCS600)
Table 3.7/10: Digital outputs Field converter mode (DCF600)
Digital inputs/outputs
Depending on the drive modes there are different
possibilities for digital inputs and outputs.
Table 3.7/7: Digital inputs Armature converter mode (DCS 600)
Table 3.7/8: Digital inputs Field converter mode (DCF 600)
II F 3-13
Digital Outputs Armature converter mode
Output
Signal use Description
DO 1 DIG_OUT 1
configurable
→
free / program. by 12.02
default: Command fans on
DO 2 DIG_OUT 2
free / program. by 12.05
default: Command field exciter
on
DO 3 DIG_OUT 3
free / program. by 12.08
default: Command main
contactor on
DO 4 DIG_OUT 4 free / program. by 14.10
DO 5 DIG_OUT 5 free / program. by 14.13
DO 6 DIG_OUT 6 free / program. by 14.16
DO 7 DIG_OUT 7 free / program. by 14.19
DO 8 DIG_OUT 8 free / program. by 14.22
Digital Outputs Field converter mode
Output
Signal use Description
DO 1 DIG_OUT 1
configurable
→
free / program. by 12.02
default: Command fans on
DO 2 DIG_OUT 2
free / program. by 12.05
default: Command field exciter
on
DO 3 DIG_OUT 3
free / program. by 12.08
default: Command main
contactor on
DO 4 DIG_OUT 4 free / program. by 14.10
DO 5 DIG_OUT 5 free / program. by 14.13
DO 6 DIG_OUT 6 free / program. by 14.16
DO 7 DIG_OUT 7 free / program. by 14.19
DO 8 DIG_OUT 8 free / program. by 14.22
Digital Inputs Armature converter mode
Input Signal use Description
DI 1 DI 1
configurable
→
12.13 ACK Converter fan
12.14 ACK Motor fan
12.15 ACK Main contactor
12.16 Emergency STOP
15.13 electrical disconnect
15.18 ACK DC breaker
15.20 ACK DYN brake
28.18 Klixon (motor 1 trip)
15.14 Main CONT ON
logical AND with
MCW 7.01 B0
15.15 Coast STOP
28.25 Klixon (motor 2 trip)
DI 2 DI 2
DI 3 DI 3
DI 4 DI 4
DI 5 DI 5
DI 6 DI 6
DI 7 DI 7
DI 8 DI 8
if COMMAND SEL 15.22 = 1 (local I/O) then
DI 6 = Reset; DI 7 = ON; DI 8 = RUN
Digital Inputs Field converter mode
Input Signal use Description
DI 2 ACK_OVERVOLT fix
Acknowledge overvoltage
protection DCF 505/506
DI 1 DI 1
configurable
→
12.13 ACK Converter fan
12.14 ACK Motor fan
12.15 ACK Main contactor
12.16 Emergency STOP
15.13 electrical disconnect
15.18 ACK DC breaker
15.20 ACK DYN brake
28.18 Klixon (motor 1 trip)
15.14 Main CONT ON
logical AND with
MCW 7.01 B0
15.15 Coast STOP
28.25 Klixon (motor 2 trip)
Note: Do not select DI 2 for
these functions!
DI 3 DI 3
DI 4 DI 4
DI 5 DI 5
DI 6 DI 6
DI 7 DI 7
DI 8 DI 8
if COMMAND SEL 15.22 = 1 (local I/O) then
DI 6 = Reset; DI 7 = ON; DI 8 = RUN