Drive control
Components required:
plastic optical fibre for distances up to 15 m
field bus module NxxA-0x; FCI (CI810);
AC70 (PM810); AC80 (PM825)
Star configuration up to 12 drives for FCI, AC70
and AC80
alternative:
APC2 + YPQ112 (max. 4 drives)
➀
Functionality:
Depends on the
field bus
module used, interface
e.g. to:
PROFIBUS with NPBA-02
MODBUS+ with NMBP-01
CS31 with NCSA-01
AF100 with FCI (CI810) or AC70 (PM810)/
AC80 (PM825)
➀
further modules on request
You will find more detailed information on data
exchange in the specific fieldbus module docu-
mentation.
Operation by PC
Components required:
plastic optical fibre for distances up to 20 m
Monitoring network up to 200 drives (same as
for ACS 600)
HCS optical fibre cable up to 200 m.
see separate manual
Configuration instruc-
tions NDBU 85-95
- Doc no.: (3ADW000100)
Functionality
:
Drives Window software package
➀
for com-
missioning, diagnosis, maintenance and trou-
ble-shooting; structure of connections see
Tech-
nical Data
System requirements/recommendation:
PC (IBM-compatible) with 486 processor or
higher (min. 50 MHz)
8 MB RAM
DOS version 5.0 or later
Windows 3.1, 3.11, Windows95; Windows
NT4.0
VGA monitor
3 1/2" floppy disk drive
PCMCIA or ISA card slot
In addition to the options provided by the
CDP312 control and display panel, there are
further functions available, and these are de-
scribed on the following page.
II F 2-13
➀
For further information see the specific publi-
cations