EasyManua.ls Logo

ABB DCS 600 - Line Reactors for Armature-Circuit Supply

ABB DCS 600
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.6 Options for the drive
Line reactors
for armature-circuit supply
When power converters are operated with thyr-
istors, the line voltage is short-circuited during
commutation from one thyristor to the next. This
operation causes voltage dips in the mains. For
the connection of a power converter system to
the mains, a decision is made between the
following configurations:
Configuration A
When using the power converter, a
minimum of 1% impedance is re-
quired to ensure proper perform-
ance of the snubber circuit. A line
reactor can be used to meet this
minimum impedance requirement.
The value must therefore not drop
below 1% u
k
(relative impedance
voltage). It should not exceed 10%
u
k
, due to considerable voltage drops which
would then occur.
Configuration B
If special requirements have to be
met at the connecting point, differ-
ent criteria must be applied for
selecting a line reactor. These re-
quirements are most often defined
as a voltage dip in percent of the
nominal supply voltage.
The combined impedance of Z
Line
and Z
LR
constitute the total series
impedance of the installation. The
ratio between the line impedance and the line
reactor impedance determines the voltage dip at
the connecting point.
9ROWDJH GLS
=
==
/LQH
/LQH /5
=
+
*100%
Example:
Maximum allowable voltage dip is 20% at the
power converter's connecting point. Above equa-
tion used and simplified to:
==
/5 /LQH
=
4*
(1)
Since the line impedance is seldom known (it can
be determined by means of a measuring routine),
and the short-circuit power at the same point is
more frequently available, the line reactor can be
calculated by means of this value.
Assumption:
The system short-circuit power at
the power converters connecting point is 180
times the power converters rated power.
The systems relative impedance voltage u
k
can
thus be determined:
X
N/LQH
==
1
180
100% 055%*.
In accordance with equation (1), the following
applies for the line reactor:
X8
N/5 ./LQH
==422%*.
Since the line reactor has to be sized specific to
a power converter , the relative variable U
k
must be converted into an absolute value. For
this purpose, the following equation applies:
X
,I/
8
N
G1 1 /5
1
=
*****
2
3
32
π
I
dN
: rated direct current
f
N
: rated frequency of the system
U
N
: rated line voltage
L
LR
: line reactor inductance
Configuration C
In the case of high power converter
outputs or high currents, a power
converter transformer must fre-
quently be used for voltage match-
ing. If an autotransformer is used
for this purpose, a commutating
reactor must additionally be used if
special conditions must be com-
plied with as per Configuration B,
the reason for this being that the u
k
of commonly used autotransform-
ers is generally too small. If you do not have to
allow for special conditions of this kind, you must
nevertheless check whether the u
k
of the au-
totransformer concerned is sufficient for satisfy-
ing Configuration A.
Connecting
point
Line
L
Line
L
LR
Connecting
point
Line
u
k
LR
ca. 1%
Connecting
point
Line
L
LR
II F 2-15

Table of Contents

Related product manuals