EasyManua.ls Logo

ABB DCS 600 - Page 20

ABB DCS 600
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DCS Type Line choke Fig.
400V-690V type
DCS60x-0025-41/51 ND01 1
DCS60x-0050-41/51 ND02 1
DCS60x-0050-61 ND03 1
DCS60x-0075-41/51 ND04 1
DCS60x-0100-51 ND06 1
DCS60x-0110-61 ND05 1
DCS60x-0140-41/51 ND06 1
DCS60x-0200-41/51 ND07 2
DCS60x-0250-41/51 ND07 2
DCS60x-0270-61 ND08 2
DCS60x-0350-41/51 ND09 2
DCS60x-0450-41/51 ND10 2
DCS60x-0450-61 ND11 2
DCS60x-0520-41/51 ND10 2
DCS60x-0700-41/51 ND12 2
DCS60x-0900-41/51/61/71 ND13 3
DCS60x-1200-41/51 ND14 3
DCS60x-1500-41/51/61/71 ND15 3
DCS60x-2000-41/51 ND16 3
Line reactors L1
Fig. 1
Fig. 2
Fig. 3
Table 2.6/1: Line reactors (for more information see
publication
Technical Data)
An examination of volume and costs results in the
following configuration:
Configuration D
If an isolation transformer is used, it
is often possible to comply with
certain connecting conditions per
Configuration B without using an
additional line reactor. The condi-
tion described in Configuration A
will then likewise be satisfied, since
the u
k
is >1 %.
With reference to the power converter:
- The line reactors listed in the table below have
been allocated to the units in accordance with
a load cycle, and are independent of the units
voltage classification. Note that the same
reactors are used for line voltages
690 V!
- For units >2000 A or >690 V, we recommend
using one isolation transformer per power
converter.
DCF 600
The line reactors in table 2.6/1 are suitable for
DCF600 three-phase field supply converters. For
full load current of the module choose the next
higher reactor type because the reactors are
dimensioned for 80% of armature current of the
DCS 600 converters.
Connecting
point
Line
II F 2-16

Table of Contents

Related product manuals