Start-up 43
26 UNRECOVER-
ABLE ERROR
Read-only. Shows information about the cause
of an unrecoverable error in the adapter
module. Bit field parameter, that is, several
status bits can be set at a time. Value 0
indicates that there are no errors.
0
ACS355:
FB PAR 26
ACSM1:
FBA PAR26
ACS850/ACQ810:
FBA par26
ACS880:
Unrecover. error
065535 Active unrecoverable errors
27 FBA PAR
REFRESH
Validates any changed adapter module
configuration parameter settings. After
refreshing, the value reverts automatically to
0 = Done.
Note: This parameter cannot be changed while
the drive is running.
0 = Done
ACS355/ACSM1:
FBA PAR
REFRESH
ACS850/ACQ810/
ACS880:
FBA par refresh
0 = Done Refreshing done
1 =
Refresh/Configure
Refreshing
No. Name/Value Description Default
Bit Name Value Description
1 DUP_MAC_ERROR 0x0001 Duplicate MAC ID error
2 RX_QUEUE_OVERRUN 0x0002 Message receive queue is full.
3 TX_QUEUE_OVERRUN 0x0004 Message transmit queue is full.
4 IO_SEND_ERROR 0x0008 Transmitting I/O data has failed.
5 CAN_BUS_OFF 0x0010 Bus-off is detected.
6 CAN_OVERRUN 0x0020 CAN message was lost.
7 DNS_RESET 0x0040 DeviceNet driver of the module is
reset.
8 DNS_BUS_SENSE_ERROR 0x0080 No voltage detected in the
network.
9 DNS_SWITCH_ERROR 0x0100 DeviceNet driver reset failed due
to an invalid MAC ID or baud rate.
13 SYS_FILE_ERR 0x1000 Initialization with the drive failed.