Start-up 45
31 D2FBA COMM
STA
Read-only. Displays the status of the fieldbus
adapter module communication.
Note: The value names may vary by drive.
0 = Idle
ACS355:
FBA STATUS
ACSM1:
D2FBA COMM
STA
ACS850/ACQ810/
ACS880:
D2FBA comm sta
0 = Idle Adapter is not configured.
1 = Exec.init Adapter is initializing.
2 = Time out Time-out has occurred in the communication
between the adapter and the drive.
3 = Conf.err Adapter configuration error: Major or minor
revision code of the common program revision
in the fieldbus adapter module is not the
revision required by the module or mapping file
upload has failed more than three times.
4 = Off-line Adapter is off-line.
5 = On-line Adapter is on-line.
6 = Reset Adapter is performing a hardware reset.
32 FBA COMM SW
VER
Read-only. Displays the common program
revision of the adapter module in format axyz,
where:
a = major revision number
xy = minor revision numbers
z = correction number or letter.
Example: 190A = revision 1.90A
N/A
ACS355:
FBA CPI FW REV
ACSM1:
FBA COMM SW
VER
ACS850/ACQ810/
ACS880:
FBA comm SW
ver
0x0000…0xFFFF Common program version of the adapter
module
No. Name/Value Description Default